TIMER CONTROL SEQUENCE OF OPERATION The pump control panel shall be equipped with four float switches to control the timed doses to be discharged. The water level must be high enough to overcome the "Redundant Off" (Bottom) float in order for the pump to be permitted to run. When the water level rises high enough to overcome the "Dose Enable" (second) float and the time clock is in a pump enable mode (pins pushed in), the pump will activate. The pump shall continue to run for the length of time as programmed on the pump run timer, and shall then shut off. The pump shall remain off until the time clock enters a new pump enable mode, at which time the pump shall activate (as long as the "Dose Enable" float is still up) and will run until the pump run timer finishes timing out. This process shall continue until the water level drops below the "Dose Enable" float and the pump run timer has timed out. The control system shall be equipped with a timer override circuit to manage peak flows and excess water use. If the water level continues to rise enough to overcome the "Timer Override" (third) float and the override selector switch is on, the pump shall be activated, regardless of the time clock position. The pump will continue to run until deactivated by the override circuit, at which time the pump will shut off and the normal pumping cycle shall resume. If the water level continues to rise enough to overcome the "High Level" (fourth) float, the audio/visual alarm shall activate until silenced by pressing the Test-Normal-Silence switch to the silence position. The alarm circuit shall automatically reset when the "High Level" float returns to its normal position. "SEPR" And "SEPRT" Simplex Series Timed Equalization Controls
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Basic Control Designation Terms: (All features and Options must be designated in model number if desired.) |
|||||
| ___SEPR___ | ______ | ______ | ___4___ | - | ______ |
| Control Series | Alarm Feature (if desired) | Breaker Feature (if desired) | Enclosure NEMA 1 Indoor NEMA Outdoor | Options (If desired) |
|
| SIMPLEX TIME DOSE SPECIFICATIONS |
![]() |
Basic "SEPR", "SEPRT", or "SEQ" Pump Control Includes:
Alarm Feature (if desired) Includes:
|
| Breaker Feature (if desired) Includes: | ||
| For units without alarm: | -Molded case pump/control circuit breaker | |
| For units with alarm: | -Molded case pump circuit breaker | |
| -Moded case alarm/control circuit breaker | ||
| For 3-phase units: | -Motor protector for pump (combination short circuit/overload) |
|
| -Molded case alarm/control breaker | ||
| ITEM | DESCRIPTION |
| SEPR-B4669 | SEPRAB124-AJLR (MULTI-FUNCTION) |
| SEPT-B4672 | SEPTAB124-AJLR (24 HOUR MULTI-FUNCTION) |
| SEQ-B4192P | SEQAB124-AJL |
|