"D"-SERIES DUPLEX CONTROLS
NEMA 1 - INDOOR
NEMA 1 - INDOOR
NEMA 4X - OUTDOOR
NEMA 4X - OUTDOOR

THREE FLOAT OPERATION
The pump control panel shall be equipped with three float switches to control, by volume, each dose to be discharged. The dosing volume is adjustable by increasing or decreasing the distance between the "Pumps Off" (Bottom) and "Pump On" (Second) float. When the water level rises high enough to overcome the "Pump On" float, the lead pump will activate and continue to run until the water level drops below the "Pumps Off" float. The control will then alternate the lead pump. If the water level continues to rise and reaches the "Lag Pump" (Third) float, the lag pump will activate the alarm and both pumps will continue to run until the water level drops below the "Pumps Off" float. The audio/visual alarm will be latched in until the alarm silence switch is pressed, at which time the audio alarm will be silenced. The visual alarm will remain lit until the liquid level drops below the "High Level/Lag" float.

FOUR FLOAT OPERATION
The alarm should be placed in the third position and the lag pump in the fourth position. If the water level continues to rise and reaches the "High Level" (Third) float, the audio/visual alarm will activate and be latched in until manually acknowledged. If the water level continues to rise and reaches the "LAG" (fourth) float, the lag pump shall activate and continue to run until the water level drops below the "Pump Off" float.

"D" Series Duplex Dose On Demand Controls

Basic Control Designation Terms:
(All features and Options must be designated in model number if desired.)
___D__________________4___- ______
Control Series
 
 
Alarm Feature
(if desired)
 
Breaker Feature
(if desired)
 
Enclosure
NEMA 1 Indoor
NEMA 4x Outdoor
(Options)
(If desired)
 

Typical Model Number - DAB124-FJL.
(Duplex control with alarm, breakers-1ph/230v, Nema 4x enclosure, flasher, upgraded contactor, and locking hasp.)

DUPLEX SPECIFICATIONS
Duplex Specs

Basic "D" Pump Control Includes:

  • Nema rated enclosure w/hinged door (Nema 1 steel or Nema 4x fiberglass)
  • Removoble aluminum backplate for component mounting.
  • Duty rated pump contactor 16A @ 115V/230V/460V
  • Electro-mechanical pump alternator
  • Lag pump float termainals
  • Hand-Off-Auto toggle switch each pump
  • Pump run indicator light each pump
  • Neatly bundled wiring harness
  • 115V control transformer w/ fused secondary
    (Three-phase units only)
  • U.L. APPROVED AND LABELED

Alarm "A" Feature (If desired) Includes:

  • 85db @ 10 ft. alarm horn
  • Test-Off-Normal toggle switch
  • High level indicator light,
    40 Watt red lexan alarm light (Outdoor units only)
  • Dry remote alarm contacts
  • 120V Powered remote alarm contacts
Breaker "B" Feature (If desired) Includes:
 For units without alarm:-Molded case pump/control circuit breaker each pump
-Molded case control circuit breaker
For units with alarm:-Molded case pump circuit breaker each pump
-Molded case alarm/control breaker
For 460v/3-phase units:   -Motor protector for pump (combination short circuit/overload)
-Molded case alarm/control breaker

ITEMDESCRIPTION
ARDAB-B2093P   ARDAB124-AFJ2KLS, AUTO REVERSING DUPLEX, 230V, 1 PH
ARDAP-B2084PARDAP384-AFJLST, AUTO REVERSING DUPLEX, 208V, 3 PH
ARDAP-B2099PARDAP324-AFJ1LST, FLA. 10-16A
DA4-B2621PDA4-J, DUPLEX W/ ALARM
DAB-B2221PDAB111-J, DUPLEX, 115V
DAB-B2240PDAB121-J, DUPLEX, 230V
DAB-B2267PDAB124-AEFJL, DUPLEX W/ ETM
DAB-B2431PDAB124-ACEFJL, DUPLEX W/ COUNTERS & ETM
DAB-B2500PDAB124-AFJL, DUPLEX
DAP-B2950PDAP321-J1, DUPLEX, 230V, 3 PHASE
DAP-B2951PDAP324-AJ1L, DUPLEX, 230V, 3 PHASE
DAP-B2952PDAP341-J1, DUPLEX, 460V, 3 PHASE
DAP-B2953PDAP344-AJ1L , DUPLEX, 460V, 3 PHASE
DAP-B2954PDAP381-J1, DUPLEX, 208V, 3 PHASE
DAP-B2955PDAP384-AJ1L, DUPLEX, 208V, 3 PHASE